Gas Insulated Switching Device & Busbar
Rated Voltage: Up to 40.5 KV
Rated Current: Up to (5000A busbar/2500A feeder)
Rated short-time withstand current, 3 s: 40 KA(3s)
Type of Switchgear: Metal Enclosed (Fix-SF6)
Classification of switchgear is according to: IEC 62271-200
Advantages:
Suitable for applications under aggressive ambient
Conditions such as : saline air humidity Dust Condensation
It is Tight to ingress of foreign object such as : Dust, Pollution, Small animal
Compact Design
Maintenance-Free Design
Extendable
Electrical data (maximum values) and dimensions |
Single-busbar and double-busbar switchgear |
Rated voltage | KV | 12 | 24 | 36 | 40.5 |
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 |
Rated short-duration Power-frequency Withstand voltage |
KV |
28 ¹⁾ |
50 |
70 |
85 ²⁾ |
Rated lightning impulse Withstand voltage |
KV |
75 |
125 |
170 |
185 |
Rated peak Withstand current |
KA |
100/104 |
100/104 |
100/104 |
100/104 |
Rated short-circuit making current |
KA |
100/104 |
100/104 |
100/104 |
100/104 |
Rated short-time Withstand current 3 s |
KA |
40 |
40 |
40 |
40 |
Rated short-circuit Breaking current |
KA |
40 |
40 |
40 |
40 |
Rated normal current of the busbar |
A |
5000 |
5000 |
5000 |
5000 |
Rated normal current of feeders |
A |
2500 |
2500 |
2500 |
2500 |
width | mm | 600 | 600 | 600 | 600 |
Depth • Single busbar • Double busbar |
Mm Mm |
1625 2665 |
1625 2665 |
1625 2665 |
1625 2665 |
Height • Standard • With high low-voltage compartment |
Mm mm |
2350 2700 |
2350 2700 |
2350 2700 |
2350 2700 |
Electrical data, filling pressure, temperature for single-busbar and double-busbar switchgear |
Common electrical data, filling pressure and temperature |
Rated insulation level |
Rated voltage U₂ | KV | 12 | 24 | 36 | 40.5 |
Rated short-duration power-frequency Withstand voltage • phase-to-earth, open contact gap • across the isolating distance |
|
28 ¹⁾ |
50 ²⁾ |
70 |
85 ³⁾ |
Rated lightning impulse withstand voltage Uᵨ: • phase-to-earth, open contact gap • across the isolating distance |
|
75 |
125 |
170 |
185⁴⁾ |
Rated frequency f₂ |
|
50/60 | 50/60 | 50/60 | 50/60 |
Rated normal current I ₂ |
For the busbar ⁹⁾ | A A A A A A |
1250 2000 2500 3150 4000 5000 |
1250 2000 2500 3150 4000 5000 |
1250 2000 2500 3150 4000 5000 |
1250 2000 2500 3150 4000 5000 |
Rated filling level p me | 70/120kpa at 20 c |
Minimum functional level p me | 50/100kpa at 20 c |
Ambient air temperature | -5 c to+55 c |
Data of the switchgear panels |
Circuit-breaker panel, discon-nector panel⁶⁾ |
Rated normal current I r⁹⁾ | A A A A A |
1250 1600 2000 2300 2500 |
1250 1600 2000 2300 2500 |
1250 1600 2000 2300 2500 |
1250 1600 2000 2300 2500 |
Rated short-time withstand current I ₖ I ₖ- 3 s | Up to kA | 40 | 40 | 40 | 40 |
Rated peak withstand current I ᵨ ⁵⁾ | Up to kA | 100/104 | 100/104 | 100/104 | 100/104 |
Rated short-circuit making current I ma ⁵⁾ | Up to kA | 100/104 | 100/104 | 100/104 | 100/104 |
Rated short-circuit breaking current I sc | Up to kA | 40 | 40 | 40 | 40 |
Electrical endurance of vacuum circuit-breakers | At rated normal current | 10,000 operating cycles |
Electrical endurance of vacuum circuit-breakers | At rated short-circuit breaking current | 50 breaking operations |
Rated filling level Pre | For feeders | 70/120 kpa at 20 c |
Minimum functional level Pme | 50/100 kpa at 20 c |
Bus section-alizer bus coupler ⁷⁾ |
Rated normal current I r⁹⁾ | A A A A |
1250 2000 2300 2500 |
1250 2000 2300 2500 |
1250 2000 2300 2500 |
1250 2000 2300 2500 |
Rated short-time withstand current I ₖ I ₖ- 3 s | Up to kA | 40 | 40 | 40 | 40 |
Rated peak withstand current I ᵨ ⁵⁾ | Up to kA | 100/104 | 100/104 | 100/104 | 100/104 |
Rated short-circuit making current I ma ⁵⁾ | Up to kA | 100/104 | 100/104 | 100/104 | 100/104 |
Rated short-circuit breaking current I sc | Up to kA | 40 | 40 | 40 | 40 |
Electrical endurance of vacuum circuit-breakers | At rated normal current | 10,000 operating cycles |
Electrical endurance of vacuum circuit-breakers | At rated short-circuit breaking current | 50 breaking operations |
Rated filling level Pre | For feeders | 70/120 kpa at 20 c |
Minimum functional level Pme | 50/100 kpa at 20 c |
Cable connection panel metering panel |
Rated normal current I r ⁸⁾⁹⁾ | A A A A |
1250 2000 2300 2500 |
1250 2000 2300 2500 |
1250 2000 2300 2500 |
1250 2000 2300 2500 |
Rated short-time withstand current I ₖ I ₖ- 3 s | Up to kA | 40 | 40 | 40 | 40 |
Rated peak withstand current I ᵨ ⁵⁾ | Up to kA | 100/104 | 100/104 | 100/104 | 100/104 |
Rated filling level Pre | For feeders | 70/120 kpa at 20 c |
Minimum functional level Pme | 50/100 kpa at 20 c |