Products

SWITCHGEARS | MV Products

MV Products

8DA10-8DB10

Medium Voltage Switchgear

Gas Insulated Switching Device & Busbar

Rated Voltage: Up to 40.5 KV

Rated Current: Up to (5000A busbar/2500A feeder)
Rated short-time withstand current, 3 s: 40 KA(3s)

Type of Switchgear: Metal Enclosed (Fix-SF6)
Classification of switchgear is according to: IEC 62271-200

 

Advantages:

  • Suitable for applications under aggressive ambient
  • Conditions such as : saline air humidity Dust Condensation
  • It is Tight to ingress of foreign object such as : Dust, Pollution, Small animal
  • Compact Design
  • Maintenance-Free Design
  • Extendable

Electrical data (maximum values) and dimensions

Single-busbar and double-busbar switchgear

Rated voltage

KV

12

24

36

40.5

Rated frequency

Hz

50/60

50/60

50/60

50/60

Rated short-duration

Power-frequency

Withstand voltage

 

 

KV

 

 

28 ¹⁾

 

 

50

 

 

70

 

 

85 ²

Rated lightning impulse

Withstand voltage

 

KV

 

75

 

125

 

170

 

185

Rated peak

Withstand current

 

KA

 

100/104

 

100/104

 

100/104

 

100/104

Rated short-circuit

making current

 

KA

 

100/104

 

100/104

 

100/104

 

100/104

Rated short-time

Withstand current 3 s

 

KA

 

40

 

40

 

40

 

40

Rated short-circuit

Breaking current

 

KA

 

40

 

40

 

40

 

40

Rated normal current

of the busbar

 

A

 

5000

 

5000

 

5000

 

5000

Rated normal current

of feeders

 

A

 

2500

 

2500

 

2500

 

2500

width

mm

600

600

600

600

Depth

Single busbar

Double busbar

 

Mm

mm

 

1625

2665

 

1625

2665

 

1625

2665

 

1625

2665

Height

Standard

With high low-voltage

compartment

 

Mm

 

mm

 

2350

 

2700

 

2350

 

2700

 

2350

 

2700

 

2350

 

2700

 


Electrical data, filling pressure, temperature for single-busbar and double-busbar switchgear

Common electrical data, filling pressure and temperature

Rated insulation level

Rated voltage U

KV

12

24

36

40.5

Rated short-duration power-frequency

Withstand voltage

phase-to-earth, open contact gap

across the isolating distance

 

 

 

 

28 ¹⁾

32 ¹⁾

 

 

50 ²⁾

60 ²⁾

 

 

70

80

 

 

85 ³⁾

90 ³⁾

Rated lightning impulse withstand voltage U:

phase-to-earth, open contact gap

across the isolating distance

 

 

 

75

85

 

 

125

145

 

 

170

195

 

 

185⁴⁾

220⁴⁾

Rated frequency f

 

 

50/60

50/60

50/60

50/60

Rated normal current I

For the busbar ⁹

A

A

A

A

A

A

1250

2000

2500

3150

4000

5000

1250

2000

2500

3150

4000

5000

1250

2000

2500

3150

4000

5000

1250

2000

2500

3150

4000

5000

Rated filling level p me

 

70/120kpa at 20 c

Minimum functional level p me

50/100kpa at 20 c

Ambient air temperature

-5 c to+55 c

 

Data of the switchgear panels

Circuit-breaker panel, discon-nector panel⁶⁾

Rated normal current I r⁹⁾

A

A

A

A

A

1250

1600

2000

2300

2500

1250

1600

2000

2300

2500

1250

1600

2000

2300

2500

1250

1600

2000

2300

2500

Rated short-time withstand current I  ₖ   I - 3 s

Up to kA

40

40

40

40

Rated peak withstand current I ᵨ  ⁵⁾

Up to kA

100/104

100/104

100/104

100/104

Rated short-circuit making current I ma ⁵⁾

Up to kA

100/104

100/104

100/104

100/104

Rated short-circuit breaking current I sc

Up to kA

40

40

40

40

Electrical endurance of vacuum circuit-breakers

At rated normal current

10,000 operating cycles

At rated short-circuit breaking current

50 breaking operations

Rated filling level Pre

For feeders

70/120 kpa at 20 c

Minimum functional level Pme

 

50/100 kpa at 20 c

 

Bus section-alizer  bus coupler ⁷⁾

Rated normal current I r⁹⁾

A

A

A

A

1250

2000

2300

2500

1250

2000

2300

2500

1250

2000

2300

2500

1250

2000

2300

2500

Rated short-time withstand current I  ₖ   I - 3 s

Up to kA

40

40

40

40

Rated peak withstand current I ᵨ  ⁵⁾

Up to kA

100/104

100/104

100/104

100/104

Rated short-circuit making current I ma ⁵⁾

Up to kA

100/104

100/104

100/104

100/104

Rated short-circuit breaking current I sc

Up to kA

40

40

40

40

Electrical endurance of vacuum circuit-breakers

At rated normal current

10,000 operating cycles

At rated short-circuit breaking current

50 breaking operations

Rated filling level Pre

For feeders

70/120 kpa at 20 c

Minimum functional level Pme

 

50/100 kpa at 20 c

 

Cable connection panel metering panel

Rated normal current I r ⁸⁾⁹⁾

A

A

A

A

1250

2000

2300

2500

1250

2000

2300

2500

1250

2000

2300

2500

1250

2000

2300

2500

Rated short-time withstand current I  ₖ   I - 3 s

Up to kA

40

40

40

40

Rated peak withstand current I ᵨ  ⁵⁾

Up to kA

100/104

100/104

100/104

100/104

Rated filling level Pre

For feeders

70/120 kpa at 20 c

Minimum functional level Pme

50/100 kpa at 20 c

 

 