Rated Voltage : Up to 17.5 KV
Rated frequency : 50/60 HZ
Rated short-duration power-frequency withstand voltage : Up to 35 KV
Rated lightning impulse withstand voltage : Up to 95 KV
Rated short-time withstand current, 3 s : 40 KA
Rated peak withstand current at 50/60 Hz : 100/104 KA
Rated short-circuit breaking current: 40 KA
Rated short-circuit making current at 50/60 Hz : 100/104 KA
Rated normal current of busbar : 3600 A
Rated normal current of feeders
– With circuit-breaker : 3600 A
– With vacuum contactor : 400 A
Type of Switchgear: Metal Enclosed (Draw out)
Classification of switchgear is according to : IEC 62271-200
Width B |
Circuit-breaker panel ≤ 1250 A 2500 A, 3150 A, 3600 A |
Up to 31.5 Ka 600 800 |
40 kA 800 800 |
Contorol Panel |
435²⁾/600 |
435²⁾ |
|
Disconnecting panel ≤ 1250 A 2500 A,3150 A, 3600 A |
600 800 |
800 800 |
|
Bus sectionalizer/circuit-breaker panel≤ 1250 A 2500 A,3150 A, 3600 A |
600 800 |
800 800 |
|
Bus sectionalizer/bus riser panel ≤2500 A 3150 A, 3600 A |
600 800 |
800 800 |
|
Metering panel |
600 |
800 |
|
Height H1 |
With standard low-voltage Compartment and IAC 0.1 s |
2253 |
2253 |
H2 |
With standard low-voltage Compartment and IAC 1.0 s |
2425 |
2460 |
H3 |
─ |
1780 |
1780 |
Depth T |
Standard |
1860 |
1860 |
Classification of the SIMOPRIME switchgear according to IEC 62271-200
Internal arc classification |
||
classification |
IAC |
|
Accessibility ─ Front ─ Rear ─ Lateral |
Type A Type A Type A |
|
Teat current Arc duration |
Ka s |
25/31.5/40 0.1/1.0 |
Classification and design |
|
Partition class Loss of service continuity category |
PM(metallic partition) LSC2B(metal-clad) |
Compartment accessibility (standard) ─ Busbar compartment ─Switching-device compartment ─ Low-voltage compartment ─ Connection compartment ─Front connection
─ Rear connection |
Tool-based Interlook-controlled Tool-based
Interlock-controlled and Tool-based Tool-based |
Electrical data(maximum values) of SIMOPRIME
Ratings |
Rated values(max.) |
Switchgear up to 7.2 kv
Rated voltage |
7.2 kV |
Rated frequency |
50/60 Hz |
Rated short-duration power-frequency withstand voltage |
20 kv¹⁾ |
Rated lightning impulse withstand voltag |
60 kv |
Rated short-time withstand current, 3 s |
40 ka |
Rated peak withstand current at 50/60 Hz |
100/104 ka |
Rated short-circuit breaking current |
40 ka |
Rated short-circuit making current at 50/60 Hz |
100/104 ka |
Rated normal current of busbar |
3600 A |
Rated normal current of feeders ─ with circuit-breaker ─ with vacuum contactor |
3600 A 400 A²⁾ |
Switchgear 12 kv
Rated voltage |
12kv |
Rated frequency |
50/60 Hz |
Rated short-duration power-frequency withstand voltage |
28 kv¹⁾ |
Rated lightning impulse withstand voltag |
75 kv³⁾ |
Rated short-time withstand current, 3 s |
40 ka |
Rated peak withstand current at 50/60 Hz |
100/104 ka |
Rated short-circuit breaking current |
40 ka |
Rated short-circuit making current at 50/60 Hz |
100/104 ka |
Rated normal current of busbar |
3600 A |
Rated normal current of feeders ─ with circuit-breaker ─ with vacuum contactor |
3600 A 400 A²⁾ |
Ratings |
Rated values(max.) |
Switchgear 15 kv
Rated voltage |
15kv |
Rated frequency |
50/60 Hz |
Rated short-duration power-frequency withstand voltage |
35 kv¹⁾ |
Rated lightning impulse withstand voltag |
95 kv³⁾ |
Rated short-time withstand current, 3 s |
40 ka |
Rated peak withstand current at 50/60 Hz |
100/104 ka |
Rated short-circuit breaking current |
40 ka |
Rated short-circuit making current at 50/60 Hz |
100/104 ka |
Rated normal current of busbar |
3600 A |
Rated normal current of feeders ─ with circuit-breaker |
3600 A |
Switchgear 17.5 kv
Rated voltage |
17.5k |
Rated frequency |
50/60 Hz |
Rated short-duration power-frequency withstand voltage |
38 kv¹⁾ |
Rated lightning impulse withstand voltag |
95 kv³⁾ |
Rated short-time withstand current, 3 s |
40 ka |
Rated peak withstand current at 50/60 Hz |
100/104 ka |
Rated short-circuit breaking current |
40 ka |
Rated short-circuit making current at 50/60 Hz |
100/104 ka |
Rated normal current of busbar |
3600 A |
Rated normal current of feeders ─ with circuit-breaker |
3600 A |